Home > Technical Data > Optical Density of Smoke
 OPTICAL DENSITY OF SMOKE
Optical Density of Smoke (ASTM E 662 - NBS Chamber)
Description of test method:
The test is carried out in a constant-condition fume cupboard by introducing the material on a suitable sample dish and heating from beneath with a small electric furnace (smouldering conditions) or with the same furnace together with a small ignition flame (flaming conditions).
The small furnace is set so that the sample receives 2.5 W/cm2 thermal energy.
The light transmission through the smoke, resulting from the burning or combustion of the sample, is detected by a photocell which senses a vertical beam of light passing trough the smoke.
The amount of light transmission passed during the test is expressed as the specific optical density value.
LATI Materials Certified:
Certificate issued in date:
12/05/89
12/05/89
12/05/89
12/05/89
23/07/91
LATENE 3
H2W-V0
LATAMID 68
H2-V0
LATAMID 66
H2 G/25-V0KB1
LATILON 28D
G/30
KELON B
FR H2 CEG/500
-V0CT3
 
Smould.
Flaming.
Smould.
Flaming.
Smould.
Flaming.
Smould.
Flaming.
Flaming.
Maximum specific optical density (Dm)
567
430
79
155
5
279
35
188
238
Time ( to reach Dm)
18:00
12:00
17:00
10:00
18:00
18:00
19:00
19:00
17:00
Corrected maximum specific optical density
552
427
72
132
1
272
33
182
201
Specific optical density at 90 secs
19
54
10
6
2
8
2
6
1
Specific optical density at 4 mins
224
219
32
80
3
31
4
9
4
Weight loss %
42
38
30
91
3
15
16
16
4

Note: Tests carried out on the account of LATI by CSI Lab. - Viale Lombardia, 20 - 20121 BOLLATE (MI)

Click here to open this guide in Acrobat Reader.
You can view or print this guide if you choose print option in Acrobat Reader.